Closed
Save

Campus Energy Management System for VA Medical Center

Veterans Affairs (VA)Sol: 36C24626B0018
est. $500K – $2M

This opportunity is closed

The response deadline has passed. Review the details for future reference or to track similar opportunities.

Quick Brief

The Department of Veterans Affairs is procuring the installation of a Campus Energy Management System at the Salisbury VAMC Campus to upgrade and consolidate existing energy management systems. The project involves replacing obsolete components with a Siemens Desigo Native BACnet system, requiring modifications to existing networks and controls, and must be completed within 365 days with a one-year warranty.

Generated 77d ago

Scope & Requirements

The project involves the upgrade and consolidation of the Energy Management Systems for Buildings 2 at the Salisbury VAMC Campus, including the installation of a new Siemens Desigo Native BACnet system.

Contract Details

Estimated Value
est. $500K – $2M
Similar contracts award $13K$126K (median $35K, 14,862 awards)Above typical range
Period of Performance
365 days
NAICS Codes
Place of Performance
Salisbury, North Carolina, United States

Agency & Contact

Contracting Organization

Agency
VETERANS AFFAIRS, DEPARTMENT OF
Sub-Agency
VETERANS AFFAIRS, DEPARTMENT OF
Office
246-NETWORK CONTRACTING OFFICE 6 (36C246)

Point of Contact

John A. Smith
Contracting Officer
(202) 555-0100

Key Dates

Project Completion Date6mo ago
Dec 12, 2025
Published4mo ago
Feb 19, 2026
Last Updated4mo ago
Feb 19, 2026
Became Solicitation4mo ago
Feb 19, 2026
Tracked
Response Due2mo ago
Mar 25, 2026

Description

W.G. (Bill) Hefner Department of Veterans Affairs Medical Center 1601 Brenner Avenue Salisbury, North Carolina 28144 Subject: Statement of Work: Install Campus Energy Management System Location: Campus Project #: 659-22-100 Date:

12 December 2025 STATEMENT OF WORK Mechanical General: The project involves the upgrade and consolidation of the Energy Management Systems (DDC) providers serving Buildings 2 on the Salisbury VAMC Campus. The new system will follow Native BACnet protocol and be able to replace existing JCI and Schneider components with a single front-end user interface compatible with Siemens. This project is to convert systems from both pneumatic controls and obsolete DDC controls to the Siemens Desigo Native BACnet central system, where applicable, for Buildings 2. This project should be completed in 365 days and include a 1 year warranty on all items.

SCOPE OF WORK: The

Scope of work associated with the project includes the following: Network & User Interface Appropriate modifications to the existing network and cabling layout (Ethernet & MSTP) for the purpose of integration, including the installation of new Desigo panels. Terminal Unit Controls

  • 1) Modifications required to replace the Tridium/Niagara controls with BACnet, Siemens Desigo compatible controllers and sensors (where required). Include in the recommendation, devices that can remain (relays, switches, valves, damper motors, sensors, etc.) To include the following:
  • (i) New Siemens server to replace the existing Siemens server.
  • (ii) Front-End Graphical User Interface modifications, including new floor plans for every level of Buildings 2.
  • (iii) Main equipment panel and controller installations.
  • (iv) Panel installations.
  • (v) Panel modifications and replacement, and controller replacements, required on the main systems.
  • (vi) Ethernet-level networking modifications.
  • (vii) BACnet MSTP networking modifications.
  • (viii) Pneumatic terminal-unit controller replacements.
  • (ix) Removal of the compressed air system serving control components and devices. to include all hardware, software, installation, wiring, cabling, programming of systems, graphics, and setup of alarms, schedules and trending; as well as networking

requirements required to into a new Siemens server in accordance with the VA standards. Applicable Codes and Standards: DVA HVAC Design Manual, March 2024 ASHRAE Standard 13 Specifying Building Automation Systems ASHRAE Standard 135 BACnet Communication Protocol IEEE 802.3 Standard for Ethernet NFPA 70 National Electrical Code EXISTING CONDITIONS Network Level