Closed
Save

Sources Sought for SEL-587Z Protective Relays

Department of Defense (DoD) > Navfac Pacific Cmd
TBD
est. $15K – $60K

This opportunity is closed

The response deadline has passed. Review the details for future reference or to track similar opportunities.

Quick Brief

The Department of the Navy is conducting market research to identify potential sources for a transformer protection relay equivalent to the SEL-587Z manufactured by Schweitzer Engineering Laboratories. The equipment will be used for the Electrical Backbone project at the Pearl Harbor Naval Shipyard and IMF. Requirements include high-impedance differential relay capabilities for bus differential protection, ground fault protection, and system monitoring.

Generated 7d ago

Scope & Requirements

Provide a high-impedance differential relay for medium- and low-voltage switchgear buses with capabilities for ground fault protection, bus monitoring, and integration with station automation systems.

Deliverables

  • Detailed technical data for product evaluation

Evaluation Criteria

  1. Technical compatibility with existing system
  2. Performance equivalence to SEL-587Z

Attachments

No files on SAM.gov

This listing does not include downloadable attachments. The solicitation details may be in the description below.

Verify on SAM.gov

Contract Details

Contract Type
TBD
Estimated Value
est. $15K – $60K
Similar contracts award $2K to $26K (median $8K, 6,256 awards)Above typical range
Incumbent Contractor
Schweitzer Engineering Laboratories (SEL)
NAICS Codes
Place of Performance
Pearl Harbor, HI, USA

Agency & Contact

Contracting Organization

Agency
DEPT OF DEFENSE
Sub-Agency
NAVFAC PACIFIC CMD

Point of Contact

John A. Smith
Contracting Officer
(202) 555-0100

Key Dates

Published8d ago
Jul 17, 2026
Last Updated8d ago
Jul 17, 2026
Became Solicitation7d ago
Jul 17, 2026
Tracked
Became Sources Sought7d ago
Jul 17, 2026
Tracked
Response Due3d ago
Jul 22, 2026
Response Datein 5d
Jul 30, 20262:00 PM HST

Description

a brand name product. The Naval Facilities Engineering Systems Command, Pacific (NAVFAC Pacific) is performing a market survey to determine if other potential sources of supply can provide a transformer protection relay that has equal performance

requirements as the SEL-587Z, manufactured by Schweitzer Engineering Laboratories (SEL), 2350 NE Hopkins Court, Pullman, WA 99163. Fiscal Year 2027 SIOP PROJECT P-8026 ELECTRICAL BACKBONE Pearl Harbor Naval Shipyard and IMF Joint Base Pearl Harbor-Hickam, Hawaii, requires the following characteristics. Provide high-impedance differential relay with the following capabilities: Bus Differential Protection – Protect medium- and low-voltage switchgear buses using high-impedance differential protection to provide high-speed detection and isolation of internal bus faults while maintaining stability during external faults and CT saturation conditions. Ground Fault Protection – Provide sensitive bus ground fault protection using high-impedance differential principles to detect low-level internal ground faults within the protected bus zone while remaining secure during external system faults. Bus Monitoring – Continuously monitor differential zone current, relay operating status, and current transformer circuit integrity to verify protection system health and ensure reliable operation of the protected bus. Reporting and Monitoring – Provide Sequential Events Recorder (SER), relay targets, alarms, and event reporting to document bus faults, trips, relay operations, and diagnostic information for post-event analysis and maintenance. Communications and Integration – Support integration with station automation and supervisory control systems through industry-standard communications protocols for remote monitoring, alarm indication, status reporting, and relay diagnostics. This notification is for market research purposes only to identify if other potential sources of supply can meet the

requirements of the Government. This is not a request for proposals, quotes, or an invitation for bid. The intent of this notice is to identify other potential sources of this product. To be considered, please submit detailed technical data for the Government to conduct a comprehensive evaluation of your manufactured product to ensure compatibility with the existing system. In accordance with FAR 15.201(e), a response to this notice is not an offer and cannot be accepted by the Government to form a binding contract. The responder is solely responsible for the information it submits and any associated costs. The Government reserves the right to disregard any submittal that is incomplete or vague. Please do not submit company brochures. Please submit complete information via electronic mail to Ms. Annette Tijerina at [email protected] no later than

30 July 2026 at 2:00 p.m. H.S.T. Any information received after the due date/time will not be considered. Any information provided to the Government in response to this RFI will become U.S. Government property and will not be returned. All proprietary or classified information will be treated appropriately. Annette Tijerina Contracting (No Street Address

2) JBPHH, HI 96860-3134 USA to this opportunity.

Get matched to contracts like this daily

Free AI-powered contract matching for your business.