The Contractor shall provide all the tools, parts, materials, equipment, labor, transportation, startup, and training for a redesigned lift station to the Commodities Maintenance Group (CMXG) at Robins Air Force Base (AFB), Georgia. These lift stations will be used to transport liquid chemical waste that could present environmental danger (i.e. acid waste, chrome waste). Each Lift Station shall have the following features: • Two (2) electric pumps made of CPVC or 316 Stainless Steel. Pump fittings must be CPVC with a two (2) inch maximum nominal size. The pump flowrate should be 25 gallons per minute per pump. The pump must have a 30-foot total dynamic head. • The tank material shall be polypropylene, with a volume of 50 to 75 gallons and a single tank containment style. • The dimensions of the lift station shall be four (4) feet long, three (3) feet wide, and four (4) feet high. • The control panel enclosure shall be made of stainless steel. • The power supply shall be 120V or 208V. • Each pump shall have disconnect switches, hands-off-auto, and level sensors for automation on/off pump operation. Phillip Braswell Alternative
Point of Contact Andrew Harth to this opportunity. CDRL A005 - Accident Incident Report.pdf CDRL A003 - Status Report_EnMS Training.pdf CDRL A004 - Contractors Safety Plan.pdf CDRL A002 - Status Report_EMS Training.pdf CDRL A001 - Commercial Drawings.pdf Solicitation - FA857126Q0079.pdf 78451 - Purchase Description (PD) - Lift Station.pdf